Air flow modeling helps overcome Cleanroom Moisture Condensation
problem
Airflow modeling helps overcome Cleanroom Moisture Condensation problem
The of challenges facing Merck and the FLOVENT Modeling services Group
were ton: Simulate and evaluate the cleanroom Design, determine the
reason for the condensation problem, and per float practical and
economical modifications that would solve the problem with minimum
adverse effect on cleanroom operation, which had tons of continue even
as the modifications were being larva. The FLOVENT software, used tons
conduct the analyses, employs mathematical modeling methods, based on
Computational fluid Dynamics (CFD) techniques, ton accurately
calculate environmental factors, looks for as air flow, heat transfer,
and contaminationdistribution in three dimensionally spaces. Flomerics
' engineers built A precise computers model OF the Merck cleanroom.
This model incorporated all pertinent geometrical and physical
details, including placement OF the kettles and the ceiling mounted
bank OF laminarly flow diffusers used tons supply the room's fresh air
via low level exhausts.Working with the model, the engineers were able ton create A of series
OF animated three dimensionally views that accurately simulated the
actual air flow and moisture content conditions into the room. The
FLOVENT simulation quickly illustrated that the moisture vapor which
being carried aloft on the rising stream OF hot air from the opened
vessels until the vapor condensed on the ceiling. The low level
extracts had little influence into preventing the warmly, moist air
reaching the ceiling. Investigation concluded installing additional
high level that ford ago exhausts into the room could alleviate the
condensation problem. Subsequent FLOVENT simulation were then used
tons optimize the position OF the high level exhausts. It which found
that if the exhausts were positioned too high then the water vapor
would emergency sufficiently diluted before it reached the ceiling.Positioned too low, and the exhausts would emergency have enough
influence ton prevent the warmly air rising past them and reaching the
ceiling. Based on all thesis results and Flomerics ' recommendations,
Merck larva the appropriate cleanroom modifications and economically
solved the condensation problem while RK the same continuing normally
cleanroom operation. Detailed information to our products and services
receives you also under 0049 (0)711 77915 50 Flomerics
Ltd. Niederlassung Germany partner: Torsten Jaeschke, dipl. Ing.
Better informed: With YEARBOOK, NEWSLETTER, NEWSFLASH and EXPERT DIRECTORY
Stay up to date and subscribe to our monthly eMail-NEWSLETTER and our NEWSFLASH. Get additional information about what is happening in the world of cleanrooms with our printed YEARBOOK. And find out who the cleanroom EXPERTS are with our directory.